To customers who own an electrochemically protected electric water heater:
January 17, 2006
<Updated 2006.1.17> <Added 2006.5.26> <Added 2007.7.10> <Added 2008.3.10> <Added 2009.6.1> <Added 2024.4.1> <Added 2024.12.24>
<2026.6.1 updated> <2026.10.23 updated>
★Added more model numbers to the list of products to be inspected (June 1, 2009)★
~Notice of Free Safety Inspection~
We would like to express our sincere gratitude for your continued patronage of our electric water heaters.
Now, regarding our electric water heaters that you use, if the cathodic protection type is not used for a long period of time (approximately 3 years or more) with the power supply and water tank still filled, there is a risk of the tank rupturing.
●If you own one of the affected electric water heaters, we will perform a safety inspection (free of charge). Please contact our dedicated service desk.
[These are installed not only in private homes, but also in government offices, schools, hospitals, and various other public facilities.]
<Target>
These are models manufactured between 1975 (Showa 50) and 1987 (Showa 62), with the following model numbers.
*Items other than those listed below are not cathodic protection type and are therefore excluded. There is absolutely no need to worry.
Please refer to the nameplate attached to the front of the electric water heater (see the nameplate for the electric water heater unit).
| S - 600 | MS - 37M1 | MS - 46E34 | RC - 30MT1 |
| ES - 601 | MS - 37M12 | MS - 46M1 | RC - 370 |
| ESD - 600 | MS - 37M21 | MS - 46M12 | RC - 370 ① |
| ESD - 601 | MS - 37M24 | MS - 46M1D | RC - 370 ② |
| MS - 30E | MS - 37M31 | MS - 46M21 | RC - 37M1 |
| MS - 30E ① | MS - 37N2 | MS - 46M24 | RC - 37M12 |
| MS - 30E ⑤ | MS - 37N2 ① | MS - 46M31 | RC - 460 |
| MS - 30E31 | MS - 37N2 ② | MS - 46N2 | RC - 460 ① |
| MS - 30E34 | MS - 37N24D | MS - 46N2 ① | RC - 460 ② |
| MS - 30E41 | MS - 37N24D ① | MS - 46N2 ② | RC - 46M1 |
| MS - 37E2 | MS - 37N24D ② | MS - 46N24D | RC - 46M12 |
| MS - 37E2 ① | MS - 46E | MS - 46N24D ① |
|
| MS - 37E31 | MS - 46E ① | MS - 46N24D ② |
|
| MS - 37E34 | MS - 46E31 | MSB - 370N |
|
★Added more model numbers to the list of products to be inspected (June 1, 2009)★
[Additional model numbers]
| MSB-250 | MSB-370 | MS-25-N2 | MWB-370 |
| MSB-250N | MSB-370E | MS-37-PK |
|
| MSB-330 | MSB-460 | MS46-PK |
|
| MSB-330N | MSB-460N | MPB-370 |
|
Previously, this was considered "exempt from inspection," but it has now been determined that a safety inspection is necessary.
Even products that have already been "inspected and checked" are being inspected again.
We sincerely apologize for the inconvenience, but we would appreciate your cooperation.
●Announcements regarding this matter were published in major newspapers nationwide by companies in the industry.
(July 1997 and February 2006)
● Survey on the installation status of electric water heaters at business establishments
Related links: http://www.jema-net.or.jp/Japanese/ha/onsui/customer.html Please take a look.
Regarding the cause of electric water heater explosions
Cathodic protection water heaters use a weak electric current (corrosion protection current) to circulate through the water in the tank to prevent rust. If the tank is left unattended for a long period without draining the water and with the cathodic protection power supply still connected, the water will decompose into hydrogen and oxygen gases through electrolysis. These gases will accumulate at the top of the tank, and it is believed that this accumulated gas will eventually cause an explosion.
If you use your electric water heater on a daily basis, there is no problem as the gas is released along with the hot water. However, if you have stopped using the hot water while using your electric water heater, we offer a free safety inspection. If you own one of the affected electric water heaters, please contact us at the number provided.
●Regarding electric water heaters manufactured by companies other than ours
Related links: http://www.jema-net.or.jp/Japanese/ha/onsui/customer.html Please take a look.
Contact information regarding this matter
◆ Contact Information
SEKISUI CHEMICAL CO., LTD.
Urban Infrastructure and Environmental Products (UIEP) Company AM Staff
[Toll-Free TEL] 0120-412-776
◆ Reception Hours
Reception hours: 9:00~24:00, 365 days a year, weekdays (except 12:00~13:00)